BVNC - Blast Valves & Dampers

BVNC overpressure blast valves are normally closed valves designed to maintain the defined differential pressure level in the shelter by releasing the air when there’s a need to release air from the gastight shelter. They provide critical protection against external blast wave while maintaining defined overpressure level.

Overview

  • A large selection of overpressure blast valves for different airflows.

  • The BVNC series includes valves with airflows in range 40-3300 m3/h (the value is at 200 Pa pressure drop per valve, several valves can be installed for larger airflow).

  • Automatic double action valves designed to protect from positive and negative phases of the blast

  • The valves are tested and certified for compliance with technical requirements of SI 4570 standard (Air ventilation and filtration systems for shelter and protected spaces).

  • The valves were approved for use by Civil Defence Command and installed in tens of thousands of shelters around the world.

  • The valves are extremely durable and can withstand heat and corrosion.

  • Simple Installation in new structures with pre-installed (cast in concrete) wall sleeves with 8-inch flanges or retrofit installation on existing walls with retrofit 8-inch flanges connected to the wall with concrete anchors.

BVNC 40.jpg

BVNC 40 - Overpressure Valve

  • Reflected pressure durability: >900 kPa

  • Nominal airflow: 40 m3/h

  • Pressure drop @ nominal: 200 Pa

  • Mechanical shock resistance: >12 g

  • Standard flange: 4 Inch

Download Files
BVNC 300 8Y LEFT SIDE VIEW.jpg

BVNC 300 - Overpressure Valve

  • Reflected pressure durability: >900 kPa

  • Nominal airflow: 300 m3/h

  • Pressure drop @ nominal: 200 Pa

  • Mechanical shock resistance: >12 g

  • Standard flange: 8 Inch

Download Files
BVNC 600 8Y LEFT SIDE VIEW.jpg

BVNO 600 - Overpressure Valve

  • Reflected pressure durability: >900 kPa

  • Nominal airflow: 600 m3/h

  • Pressure drop @ nominal: 200 Pa

  • Mechanical shock resistance: >12 g

  • Standard flange: 8 Inch

Download Files
BVNC 1500 8Y,2100 14Y ,3300  14Y  LEFT SIDE VIEW.jpg

BVNO 1500 - Overpressure Valve

  • Reflected pressure durability: >900 kPa

  • Nominal airflow: 1500 m3/h

  • Pressure drop @ nominal: 200 Pa

  • Mechanical shock resistance: >12 g

  • Standard flange: 8 Inch

Download Files
BVNC 1500 8Y,2100 14Y ,3300  14Y  RIGHT SIDE VIEW.jpg

BVNO 2100 - Overpressure Valve

  • Reflected pressure durability: >900 kPa

  • Nominal airflow: 2100 m3/h

  • Pressure drop @ nominal: 200 Pa

  • Mechanical shock resistance: >12 g

  • Standard flange: 14 Inch

Download Files
BVNC 2100 14Z, 3300 14Z LEFT SIDE VIEW.jpg

BVNO 3300 - Overpressure Valve

  • Reflected pressure durability: >900 kPa

  • Nominal airflow: 3300 m3/h

  • Pressure drop @ nominal: 200 Pa

  • Mechanical shock resistance: >12 g

  • Standard flange: 14 Inch

Download Files
PRV 800 LEFT SIDE VIEW.jpg

PRV 800 - Differential pressure Valve

  • Regulated airflow: 50-800 m3/h

  • Mechanical shock resistance: >12 g

  • Standard flange: 8 Inch

Download Files

BVNC Blast Valves Series

Preparation for Installation of BVNC Valves

Definitions:

  • Air inlet – ventilation opening in the shelter perimeter wall intended for pulling fresh air from outside.

  • Air outlet – ventilation opening in the shelter perimeter wall intended for releasing air from the shelter.

  • Blast valve – a protective device designed for installation on/in the air inlet for protecting the internal space and the system components from blast wave pressure.

  • Overpressure valve – a protective device designed for installation on/in the air outlet for controlled release of air from the shelter and maintenance of overpressure levels in the protected space.

  • Flange – devices for connection of air duct or valves.

Wall Sleeve with Flange - for Casting in Concrete Walls

Wall sleeves are hollow pipes which are intended to be casted in shelter concrete walls for allowing passage of air from outside and inside. Wall sleeves are usually connected with flanges on the shelter side to allow simple connection of the blast valve, overpressure valve, gas tight valve, air duct, cable gas tight passages and more.​​

* wall sleeves are not included in the kit and can be purchased separately.

wall_sleeve_8_edited_edited.png

Retrofit Flange​ - for Installation with Anchors on Existing Walls